CUMMINS 1000kw Diesel Generator Set from China
CUMMINS 1000kw Diesel Generator Set for Landuse

Engine of CUMMINS E1000GL Diesel Generator Set for Landuse

Engine model CCEC CUMMINS KTA50-G3
No. of cylinders 16(V-line)
Displacement(L) 50.3
Induction system Exhaust turbocharged,   water-air inter-cooling
Combustion system PT type fuel pump
Bore*Stroke(mm) 159*159
Compression ratio 13.9:1
Rated speed(rpm) 1500
Maximum power(KW/HP) 1227/1669
speed control system  High precision electrical speed governor
exhaust smoke level (m3/min) 4529
Exhaust temperature (°C) 585
Maxium exhaust back pressure(kPa) 10
Maxium intake pressure(kPa) 6.23
Air consumption(m3/min) 1643
Air flow(m3/min) 30425
100% load fuel consumption(L/H) 254
The total capacity of oil(L) 177
Oil consumption(g/kwh) ≤4
Oil sump capacity(L) 151
Rated oil pressure(kPa) 345-483
Coolant capacity (engine and radiator) (L) 279
Thermostat opening temperature(°C) 82-93
Maximum water temperature(°C) 104
   

Alternator of CUMMINS E1000GL Diesel Generator Set for Landuse

Alternator model(Stamford) HCI634G
Alternator model(Marathon) MX-1030-4
Alternator model (Engga) EG400L-1000N
Phase 3
Winding connection 4 wire 3 phase ,Y type
Starter battery capacity(Ah) 195*4
Starter battery voltage(V) 24
No. of bearings 1
Power factor 0.8
Protection class IP23
Altitude requirement(m) ≤1000
Excitation mothod Brushless 
Insulation class /temperature class H/H
Steady-state voltage reguation ≤±1%
Alternator capacity 1260KVA
Alternator efficiency 0.948
Cooling air flow(m3/s) 2.69
voltage regulate range ≥±5%
Steady-state voltage reguation ≤±1%
Transient voltage deviation(100% sudden power reduction) ≤+25%
Transient voltage deviation(sudden power incremen) ≤-20%
Voltage stabilization time (100% sudden power reduction)(S) ≤6
Voltage stabilization time (sudden power increment) (S) ≤6
Steady-state frequency regulation 0-5% adjustable
Frequency volatility ≤0.5%
Transient frequency deviation (100% sudden power reduction) ≤+12%
Transient frequency deviation (sudden power increment) ≤-10%
Frequency recovery time(100% sudden power reduction)(S) ≤5
Frequency recovery time (sudden power increment)(S) ≤5
   

CUMMINS E1000GL Diesel Generator Set for Landuse

Model E1000GL
Continous output(50Hz) 1000KW/1250KVA
Standby output(50Hz) 1100KW/1375KVA
Rated frequency(Hz) 50/60
Open type external dimension of base fuel tank(mm) 5200*2100*2600
Net weight (kg) 9150
Silent type external dimension(mm) NONE
Weight(kg) NONE